Your Inspection Co.
API Inspection / Repair Recommendation
| Site | Calder Bay Complex | RR # | RR-019-PSV-14308 |
|---|---|---|---|
| Equipment ID | PSV-14308 | ||
| Process Description | Pump Discharge | ||
| Inspector | Hollis B. | ||
| Date of Finding | 4/24/26 | ||
| EWO / Client WO # | — |
FINDINGS:
During the 2026 U14 Turnaround, visual inspection of PSV-14308 (Pump Discharge) revealed: WFMT found a 1.5 in. linear indication at the toe of the N3 nozzle-to-shell weld.
RECOMMENDATIONS:
Grind out and re-inspect. If the indication remains past 1/8 in., repair per the weld procedure and re-test.
JUSTIFICATION(S):
No justification recorded.
PHOTO REFERENCE:
No photos attached.