Client deferred
Written 11/21/26 by Priya N.
Findings summary
Pitting up to 0.090 in. deep in a 6 in. x 8 in. area at the 6 o'clock position of the bottom head. Remaining wall 0.410 in. against a 0.375 in. minimum.
Formal write-up
Title
Localized pitting at bottom head
Cause
Corrosion
Findings
Pitting up to 0.090 in. deep in a 6 in. x 8 in. area at the 6 o'clock position of the bottom head. Remaining wall 0.410 in. against a 0.375 in. minimum.
Measurements
—
Recommendation
Clean to bright metal, weld overlay the pitted area, PT after repair.
Justification
—
NotesNot printed
—